Indoor or outdoor coolroom: choosing the right spot on your site
How indoor and outdoor coolrooms compare on weather, sun, deliveries, plant heat, noise and permits, with a sheet to score each spot on your site.
Last updated
Put the coolroom indoors if you have the floor space and somewhere for the plant's heat to go: it is sheltered, closer to where staff work and takes less heat from the sun. Go outdoors when the space inside is worth more to you than that, or the room is bigger than the building can take. An outdoor room needs a roof, a base that drains, a longer walk for staff and, as a new structure, it may need permits. To choose between the spots you have, score each on five things: weather exposure, the delivery route, where the heat goes, working access and the services nearby.
How to use this guide
Step 1: Look at each spot
Weather, deliveries, heat, access and services, one site at a time.
Go to ScoringStep 2: Score them
Fill in the site comparison and mark what the designer has to confirm.
Go to the recordStep 3: Call
Bring the comparison to the site assessment, or read it out when you call.
Call (03) 5153 2650
How an indoor and an outdoor coolroom compare
| Point | Indoor room | Outdoor room |
|---|---|---|
| Weather | Sheltered by the building. | Needs a roof and a base that rain drains away from. Whether a panel room can stand outside, and with what roof, is for the panel maker to say. |
| Sun | Shaded by the building. | The roof, and the walls that catch morning and afternoon sun, add to the heat the plant has to remove. |
| The air at the door | Whatever the room around it is: cool in an air-conditioned corridor, hot beside a kitchen. | The yard's air, which on a hot day adds to the load every time the door opens. |
| The plant's heat | A one-piece unit pushes its warm air into the building. A split system can send it outside. | Goes outside with the plant, which still needs free air around it. |
| Floor space | Takes floor space inside. | Frees it, and needs a level base of its own. |
| Staff and deliveries | Usually a short walk under cover. | A longer walk, often in the open, and a delivery route of its own. |
| Permits | Ask whether the work needs a building permit, and ask the food regulator about the fit-out. | The same questions. Constructing a building is also one of the common reasons a planning permit is needed. |
| Sound | A one-piece unit on the room makes its sound inside the building. | Plant sound that reaches nearby homes is measured against the noise limits for businesses. |
The kinds of plant, one-piece, split and rack, are explained on the coolroom installation page. This guide is about where the room and its plant should go.
Can a coolroom go outside?
It can, if the room is built for it. Some panel rooms are made for indoor use only, and others are made to stand outside with a roof over them. The panel maker's documents for your panels say which yours are, and what roof, base and finish an outdoor room needs. There is no single outdoor specification, so ask for it in writing with the quote.
| What weather does | What to look at on the spot |
|---|---|
| Rain at the base of the walls | Water has to drain freely away from the panels, most of all at their base, where it can get into the insulation. Water that gets in and freezes makes a panel bulge. Look at which way the ground falls and where rain from nearby roofs lands. |
| Wet insulation | Insulation only works dry. Seals around the panels have to stay intact and keep out the water used for cleaning as well as the rain. |
| Sun on the plant | A condensing unit is best kept out of long spells of direct sun, but whatever shades it must not block its air. How a unit is shaded follows its manual. Refrigerant pipes and their insulation should be kept out of direct sun where possible. |
| Pests | A food premises has to keep pests out, and give them nowhere to live, as far as practicable. A gap under an outdoor room, or an unsealed hole where pipes go through a wall, is the kind of place to check. |
| Dust | Dust clogs a condenser, so a dusty spot is a poor one for the plant. Note whether trucks or machinery raise dust nearby. |
Sun on the roof and the summer heat load
When we work out the heat a room has to shed, a room in the sun gets an allowance on top of the air temperature around it. The roof takes the largest allowance by far, because it faces the sun all day. Walls that catch the low morning and afternoon sun come next. A light-coloured surface takes about half the allowance of a dark one.
- Shade the roof. A roof over the room, or shading, cuts the heat load a great deal.
- Choose light colours. A lighter roof absorbs less of the sun's heat than a darker one.
- Leave a gap at sunny walls. Stack stock a little further off a wall that takes the sun: 10 to 15 cm, against at least 10 cm off the other walls.
- Deal with the exposure first. Cutting heat gain from the sun is one of the simplest ways to reduce what refrigeration uses. Do it before deciding the room needs more plant.
Delivery routes and staff travel
Food is best kept moving one way: in from the delivery, into storage, then to preparation and out. Safe Food Australia's guide to the food premises standard (opens in a new tab) says equipment should sit where staff can readily use it. It makes the point with a coolroom set some distance from a stall: if staff do not have time to walk to it, food can be left out of temperature control.
- The path from the truck. Short, level and wide enough for what arrives. A route that crosses a preparation area is worth avoiding.
- The door. It opens many times a day, and each time it lets in the air outside it. Frequent opening on a hot day adds a lot of load. A small door for people beside a wide door for pallets can cut the cold air lost.
- Time in the cold. The fewer and shorter the trips staff make into the room, the better, for them and for the running cost.
- Out of sight. A room across the yard is one where a person working alone is out of view, and a mobile phone may not work inside a coldroom. The door release and alarm inside the room matter more there.
A coolroom in a small loading yard
In a tight yard the room, its plant and the trucks all want the same space. Before choosing a spot, check these:
- whether a truck can still turn, back in and unload with the room in place
- whether the plant has clear air on every side and nothing parked against it
- whether forklift tines or a reversing truck could hit the room or the pipes. A punctured panel lets moisture in, and refrigerant pipes must not be run where they can be damaged unless they are protected
- whether loading docks and cooling units sit away from where food is prepared
- whether deliveries arrive at night near homes: EPA Victoria counts night-time vehicle movements and loading among the noises that disturb sleep
Where the heat goes, and room to service the plant
Refrigeration moves heat out of the room and puts it somewhere else. Where that somewhere is decides a lot.
- A one-piece unit indoors sends its warm air out of the side that faces away from the room, into the space around it. That space needs air moving through it, and if it is a kitchen or a shop, the room's heat becomes that room's heat.
- A condensing unit needs a steady supply of outside air and a way for the warm air to get away without being drawn back in. Without that it runs at higher pressures, works poorly and can fail.
- Clearances come from the unit's manual. As a guide, allow about the width of the unit on each side, and more where walls close it in on three sides.
- Hot spots shrink capacity. A unit chosen for normal conditions can be too small on a hot roof, in a poorly ventilated corner or in a hot plant room. Tell us where it would sit.
- Room to work. Leave room on every side of the plant for a technician to service it and clean its condenser. Plant on a roof or a high wall needs a safe way up.
- Short pipe runs. For a split system, keep the pipes between the two units as short and direct as the site allows.
Next to a kitchen or other heat
Keep a coolroom and its plant away from heat sources. A wall shared with a cooking line, a dishwasher or a hot plant room lets more heat into the room than a wall facing a cool store, because the heat through each wall depends on the temperature on its other side. A one-piece unit on that wall breathes hot air. A condensing unit should not sit near steam, hot air or fume exhausts, and refrigerant pipes should not run past furnaces or boilers.
Noise near homes
Refrigeration plant runs at night as well as by day, and a steady hum is the kind of noise people notice. EPA Victoria (opens in a new tab) says noise limits apply to commercial premises of all sizes, and that they depend on the zoning, where the nearest noise-sensitive places such as homes are, the background noise and the time of day. Its guidelines (opens in a new tab) put night at 10 pm to 7 am. Mount plant away from bedrooms and other noise-sensitive spaces where you can. Ask for the plant's sound level and where it would sit, and raise the nearest homes at the site assessment. EPA Victoria notes that the limits are not set to make a business inaudible.
Permits for a coolroom outside
A room outside is new building work. East Gippsland Shire Council says almost all building works require a building permit (opens in a new tab), that private building surveyors issue them in the shire, and that some minor work is exempt. Whether your room is exempt is for the building surveyor to say. The council also lists constructing a building among the common reasons a planning permit (opens in a new tab) is needed, and reminds owners that a planning permit is not a building permit.
For a food business, the guide to converting a storeroom into a coolroom says who to ask about the fit-out. If you lease the premises, see the guide to installing a coolroom in leased premises.
How to score each spot on your site
Give each spot a name, such as "storeroom off the kitchen" or "against the back wall outside", and score it on the five rows below. The score is a planning aid. The site assessment settles the choice.
| Row | Easier when | Harder when |
|---|---|---|
| Weather exposure | Inside, or outside under a roof with shade on the roof and the sunny walls, on ground that drains away. | Outside in full sun, with water pooling at the base or dust blowing through. |
| Delivery route | A short, level path from the delivery point that does not cross food preparation, with a door suited to the load. | A long or stepped route, through preparation areas, or unloading next to homes at night. |
| Where the heat goes | The plant has open air on every side, nothing overhead, no exhausts nearby, and its warm air is not blowing into a work or customer area. | The plant is boxed in on three sides, under a low roof, near a kitchen exhaust, or close to a neighbour's bedroom. |
| Working access | Staff reach the room under cover in a short walk, and the plant can be reached from the ground with room to work. | A long walk in the open, a room out of sight, or plant that can only be reached by ladder or by moving stock. |
| Services nearby | Power and a drain close by, a short pipe run, and firm, level ground for the plant. | No supply nearby, nowhere for water from the evaporator to go, a long or exposed pipe run, or soft or sloping ground. |
Coolroom site comparison
What happens at the site assessment
We look at the spots you have scored, work out the heat load for the one you prefer, and match the plant to it. Our coolroom installation page covers what the site needs, the stages of a build and what drives the cost. Bring the comparison, or have it in front of you when you call.
If a room you already have could take the coolroom, see the guide to converting an existing room into a coolroom. If you are still deciding between a room and cabinets, see the guide to a coolroom or commercial fridges.
Sources (19)
Checked on 19 November 2026
- Australian Government, energy.gov.au: refrigeration guide for businesses (opens in a new tab)
- Postharvest management of vegetables (Hort Innovation): cool rooms (opens in a new tab)
- Food Standards Australia New Zealand: Safe Food Australia, chapter 3.2.3, food premises and equipment (opens in a new tab)
- Australia and New Zealand refrigerant handling code of practice, part 2, 2025 edition (opens in a new tab)
- BlueScope: technical bulletin 31, COLORBOND Intramax steel for coolroom panels, December 2020 (opens in a new tab)
- BlueScope: solar absorptance of COLORBOND steel colours, updated March 2023 (opens in a new tab)
- Heatcraft: installation and operations manual for condensing units, September 2026 (opens in a new tab)
- Danfoss: Optyma Slim Pack condensing units, instructions, 2024 (opens in a new tab)
- Danfoss: cold room system design and component selection (opens in a new tab)
- HTPG Russell: refrigeration engineering manual, RU-ENG-0313A (opens in a new tab)
- Heatcraft: refrigeration load estimate form for rooms above freezing (opens in a new tab)
- TEFCOLD: cold room panels 80 mm, product sheet (opens in a new tab)
- KPS Global: outdoor walk-in coolers basics, 4 April 2023 (opens in a new tab)
- Daikin: monoblock refrigeration unit explained (opens in a new tab)
- SafeWork SA: cold storage facilities (opens in a new tab)
- EPA Victoria: commercial, industrial and trade noise, updated 17 March 2026 (opens in a new tab)
- EPA Victoria: commerce, industry and trade noise guidelines, 2 May 2025 (opens in a new tab)
- East Gippsland Shire Council: building permits (opens in a new tab)
- East Gippsland Shire Council: planning permit overview (opens in a new tab)
Related pages
- Installing a coolroom in leased premises: the permission and project brief
If the landlord has to agree to the spot and the plant.
- Converting an existing room into a coolroom
If a room you already have could take the coolroom.
- Coolroom or commercial fridges: choosing storage format and capacity
If you are still deciding between a room and cabinets.
Choosing where a coolroom goes?
Send ABL your site comparison with an enquiry, or call and talk it through.
Filled in the record? Copy or print it first: it is not sent with a call or an enquiry.