Coolroom or commercial fridges: choosing how to store your stock
How a walk-in coolroom and commercial fridges compare on usable space, staff travel, kitchen heat, breakdowns and cost, with a stock matrix to fill in.
Last updated
A coolroom suits a business that holds a lot of stock at one temperature, takes it in bulk and reaches into it a few times a shift. Commercial fridges suit stock that is picked all day where it is used, stock that needs several different temperatures, and a business that wants a breakdown to touch only part of its stock. The two also work together: a room for bulk and cabinets where the food is prepared. Your own stock decides which, so list it by temperature, by the box it comes in and by how often you reach for it.
How to use this guide
Step 1: List your stock
Each line by temperature, the unit it comes in and how often it is picked.
Go to Stock linesStep 2: Fill in the matrix
Then compare a room with cabinets on space, travel, heat and breakdowns.
Go to the recordStep 3: Call
Bring the matrix to the site assessment, or read it out when you call.
Call (03) 5153 2650
How a coolroom and commercial fridges compare
| Point | Coolroom | Commercial fridges |
|---|---|---|
| What it is | An insulated room you walk into, cooled by its own refrigeration plant. | Cabinets that carry their own refrigeration, built into or onto the cabinet. Remote cabinets, run from plant elsewhere, also exist. |
| Temperatures | One temperature per room. A second temperature means a second room or a separate side. | Each cabinet holds its own temperature. |
| What fits | Cartons, crates and bulk packs on shelving, off the floor. | What fits the shelves: the shelf size and the weight each shelf takes set the limit. |
| Staff | Walk into the cold to pick, and out again. | Reach in at the point of use. |
| Heat | Goes wherever the plant puts it. A split system can send it outside. | A self-contained cabinet puts its heat into the room it stands in. |
| A breakdown | Puts all the room's stock at risk at once. | Puts one cabinet's stock at risk. |
| Upkeep | One plant to service, with its door, seals and drain. | A condenser on every cabinet to keep clean, often monthly. |
| Energy figures | Worked out for your room: there is no label to compare. | Cabinets have to meet minimum energy standards, and each has a tested daily energy figure, so two can be compared like for like. |
Once cabinets are the answer, the guide to choosing a commercial fridge format compares uprights, underbench fridges, drawers and roll-ins.
Start with your stock
The answer comes from what you store, not from the size of the business. For each line of stock, note four things: the temperature it needs, the unit it arrives in, how many of those units you hold at your busiest, and how often someone fetches from it in your busiest hour. Potentially hazardous chilled food is kept at 5°C or below, and frozen food stays frozen hard, as Food Standards Australia New Zealand (opens in a new tab) explains.
| What you find | What it points to |
|---|---|
| Most of the stock needs one temperature | One room can hold it. |
| Lines need different temperatures | More than one space. Produce alone runs from 0°C for broccoli and carrots to 10°C or more for cucumbers and eggplant. |
| Raw meat or seafood alongside ready-to-eat food | Raw food stored separately from ready-to-eat food, or below it: separate cabinets, or shelving in a room planned with raw food at the bottom. |
| Fruit stored with vegetables | Some fruit, such as apples, keeps giving off ethylene even near 0°C, and ethylene does vegetables no good. Separate spaces help. |
| Large or heavy units: cartons, crates, carcasses | A room. Cabinet shelves limit the size and the weight of what goes on them. |
| Small amounts reached for all day | Cabinets at the point of use. |
| Stock that arrives warm, or is cooked and cooled on site | Plant sized for it. Storage cabinets are built to hold food that is already cold, not to cool it. |
How much space can you actually use?
Neither a room nor a cabinet can be packed to its walls. Cold air has to move around the stock, or the food does not stay cold.
| In a coolroom | In a commercial fridge |
|---|---|
| A gap between stock and the walls, at least 10 cm, so air can circulate. | Usable volume runs from the floor grid to the load line, which is less than the gross volume on the label. |
| Clear air under the fan unit, 25 cm or more above stacked stock. | A gap at the back and top so air can move. The manual for the model gives the figure. |
| Food stored off the floor. | Stock on the shelves, not the cabinet floor, and no more weight per shelf than the manual allows. |
| Aisles to walk and turn in, and the warmer spots by the door and in back corners. | Door swing and room to open drawers in front of the cabinet. |
Measure in shelf space rather than cubic metres: the shelf length and depth you need for your busiest week. A room or a fridge that is overstocked cannot chill the food in it to the right temperature. Safe Food Australia's guide to the food premises standard (opens in a new tab) asks for enough refrigerated space for the volume of food, and its example is a café that adds catering and finds no room left in its coolroom for the extra fillings and salads.
Staff workflow and how often you pick
- Every opening lets heat in. Warm air comes in each time a door opens, whether it is a coolroom door or a cabinet door. A room fetched from many times an hour needs a fast-closing door or strip curtains, and plant sized for the traffic.
- Walking adds up. A room down a corridor costs a walk every time, so count the trips. The items fetched most often belong near the bench.
- Time in the cold. SafeWork SA (opens in a new tab) advises keeping time in coldrooms as short as possible, and suggests considering upright or deep freezers instead of walk-in coldrooms to cut exposure to the cold. WorkSafe Victoria (opens in a new tab) asks for walk-in freezers to have two-way door catches and an alarm so nobody is trapped inside.
- Carrying. Plan a route a trolley can use, and shelves that keep heavy, often-used items between shoulder and mid-thigh height.
- One way through. Food is best kept moving one way, from storage to preparation, without staff crossing back through other areas.
Where does the heat go?
A self-contained commercial fridge pumps the heat it removes out into the room it stands in. In a small room without ventilation, cabinets quickly make the room hotter, and then they use more power. A freezer cabinet gives off more heat and uses much more energy than a fridge cabinet of the same size: on one matching pair of uprights, more than three times as much. Check the heat rejection and the energy figure on each cabinet's specification sheet.
- Climate class. Each cabinet is rated for a room temperature range, shown as its climate class on the label. It has to stand somewhere within that range, so note how hot the kitchen gets on a busy summer day.
- Placement. Keep cabinets away from ovens, fryers, warm draughts and walls that take the sun.
- A coolroom's heat goes wherever its plant is. A split system can put it outside. A one-piece unit puts it beside the room. The guide to an indoor or outdoor coolroom covers where that heat should go.
Upkeep, and what one breakdown does
A row of cabinets is a row of separate refrigeration systems. When one stops, its stock moves to the others and the rest of the kitchen carries on. When a coolroom stops, everything in it is at risk at once, so a business with one room needs a plan for where that stock goes.
| Point | Coolroom | Commercial fridges |
|---|---|---|
| Routine cleaning | The condenser and the evaporator, on a service schedule. | Each cabinet's condenser coil and filter, often monthly. The manual for each model gives the interval. |
| Door seals | One door, or two if there is a freezer side. | A seal on every door and drawer. |
| If the refrigeration stops | The whole room is affected. Monitoring with an alarm gives warning. | Only that cabinet is affected. |
| Building in a backup | Separate systems for separate rooms, rather than one shared plant, keep service simple and give some redundancy. | Built in: there are several systems already. |
For an alarm that warns when a room or cabinet drifts, see the temperature monitoring page.
One room or two, and chilled with frozen
Split stock into separate rooms when it needs different temperatures, when raw and ready-to-eat food have to be kept apart, or when fruit would sit with vegetables. Otherwise one room is usually the more efficient choice: for the same floor area, two small rooms need more refrigeration than one larger room, because each has more wall for what it holds and its air is changed more often.
A combined chiller and freezer room
A combined room saves space, but it is really two rooms with two refrigeration systems and a shared wall, and each system needs servicing. When the freezer is entered through the chiller, the chiller acts as an anteroom and less warm air reaches the freezer. The shared wall separates the coldest and the warmest sides, so it carries the biggest temperature difference in the room. Frost on the freezer door or moisture on the chiller door is a sign the door seals need attention.
Partitioning a room you already have
A partition makes two storage conditions only if each side has its own cooling and its own control. A coolroom and a freezer need different evaporators, compressors, defrost and controls. A partition between a chilled side and a frozen side carries a bigger temperature difference than one between two chilled zones, so its insulation is a design question for the site assessment, not a wall of shelving and a curtain.
Adding frozen storage to a chilled business
Frozen storage is a different design, not a colder setting. A freezer room needs thicker panels than a coolroom, at least R6 against at least R4.5, and an insulated floor, often with heating under it so the ground below does not freeze and lift the slab. Freezing product also takes more refrigeration than chilling it. So a coolroom does not become a freezer by changing its setting: a room built for chilled storage needs a fresh design and a fresh cost assessment before it holds frozen stock.
| Point | Reach-in freezer cabinets | Walk-in freezer |
|---|---|---|
| Energy and heat | Each uses much more energy than a fridge cabinet of the same size, and puts its heat into the kitchen. | Worked out for the room. Its plant's heat can go outside. |
| Staff | No one walks into the cold. | Staff work inside at freezer temperature, so time inside, clothing, the inside door release and the alarm all matter. |
| Power | The manual may ask for a circuit of its own for each cabinet, and a freezer cabinet can draw more current than the matching fridge. | Plant and supply sized at the site assessment. |
| Space | Fits along a wall or under a bench. | Needs its own floor area, panels and insulated floor. |
Freezer space for buying in bulk
Buying in bulk needs space that keeps the stock safe until it is used. Follow the storage instructions on each product, rotate older stock first, and accept frozen deliveries only if they arrive frozen hard. Storage freezers are built to hold food that is already frozen, not to freeze it. Plan chiller space too: large frozen items can take several days to thaw in a fridge. Smaller cartons are easier to lift and stack than bulk packs.
Planning for growth and longer hours
- Size for what you can see coming, not more. An oversized room costs more to build and more to run. Plan for your needs now and over the next few years, and design for how the plant runs at part load.
- Leave a way to grow. ABL's modular panel rooms can be relocated or expanded as a business grows. A cabinet layout grows a cabinet at a time, if the power and the floor space are there.
- Longer hours mean more load. More trading hours mean more door openings and more warm product going in. Heavy use can double the warm air that comes in through the door. Plant chosen for the old hours can struggle with the new ones, so tell us how your hours are changing.
What does a coolroom cost?
As a general guide, as at November 2026, ABL's published prices put a small walk-in chiller of about 5 cubic metres at around $8,000 to $12,000, and larger custom rooms at around $15,000 to $50,000 or more. Your quote is the price, and it depends on the size, the temperature, the insulation, the refrigeration, the shelving and lighting, and whether it is a new build or a retrofit. The coolroom installation page explains what drives each of those.
Cabinets are priced by number and kind, so the matrix below is what a cabinet quote starts from. ABL also supplies commercial refrigeration equipment: see the equipment supply page. When you compare, count the running cost too: each cabinet's energy figure, and the extra heat in the kitchen.
Stock and storage matrix
What to bring us
Bring the matrix to the site assessment, or read it out when you call. From it we size a room to your stock, or work out the cabinets it would take. Our coolroom installation page has a project brief for the room itself, and the guide to an indoor or outdoor coolroom helps choose where it stands.
Sources (25)
Checked on 19 November 2026
- ABL Refrigeration: commercial refrigeration services (opens in a new tab) ABL's own page.
- Australian Government, energy.gov.au: refrigeration guide for businesses (opens in a new tab)
- Food Standards Australia New Zealand: storing food safely (opens in a new tab)
- Food Standards Australia New Zealand: Safe Food Australia, chapter 3.2.2 (opens in a new tab)
- Food Standards Australia New Zealand: Safe Food Australia, chapter 3.2.3, food premises and equipment (opens in a new tab)
- Federal Register of Legislation: Greenhouse and Energy Minimum Standards (Refrigerated Cabinets) Determination 2024 (opens in a new tab)
- SafeWork SA: cold storage facilities (opens in a new tab)
- WorkSafe Victoria: injury hotspots for chefs and cooks (opens in a new tab)
- Postharvest management of vegetables (Hort Innovation): storage temperatures (opens in a new tab)
- Postharvest management of vegetables (Hort Innovation): ethylene (opens in a new tab)
- Postharvest management of vegetables (Hort Innovation): cool rooms (opens in a new tab)
- Electrolux Professional: ECOguide to professional refrigeration, 2020 (opens in a new tab)
- SKOPE: ReFlex storage cabinets user guide, October 2021 (opens in a new tab)
- SKOPE: ReFlex upright fridge specification sheet, November 2021 (opens in a new tab)
- SKOPE: ReFlex upright freezer specification sheet, August 2020 (opens in a new tab)
- Williams Refrigeration Australia: operator and user manual, April 2020 (opens in a new tab)
- Bromic: underbench fridges manual, June 2022 (opens in a new tab)
- True Manufacturing: T-series reach-in installation manual, July 2021 (opens in a new tab)
- Heatcraft: refrigeration load estimate form for rooms above freezing (opens in a new tab)
- Heatcraft: refrigeration load estimate form for rooms below freezing (opens in a new tab)
- Heatcraft: engineering manual H-ENGM0408, April 2008 (archived copy) (opens in a new tab)
- Danfoss: cold room system design and component selection (opens in a new tab)
- KPS Global: what to consider when modifying a walk-in, 18 March 2025 (opens in a new tab)
- Foodservice Equipment and Supplies: service tips for combined walk-in coolers and freezers (opens in a new tab)
- NSW Government: industrial refrigeration guide, 2017 (opens in a new tab)
Related pages
- Upright, underbench, drawer or roll-in: choosing a commercial fridge format
Once cabinets are the answer, choose the kind.
- Indoor or outdoor coolroom: choosing a location
Where a room and its plant should go.
- Comparing commercial refrigeration energy ratings and running costs
Compare cabinets on what they cost to run.
Deciding between a coolroom and fridges?
Send ABL your stock matrix with an enquiry, or call and talk it through.
Filled in the record? Copy or print it first: it is not sent with a call or an enquiry.