Choosing commercial refrigeration temperature monitoring: specify it, then test it

How to choose temperature monitoring for commercial refrigeration: what to measure and where, outages, alerts, records, calibration and the handover test.

Last updated

Choose temperature monitoring by the decisions it has to support, not by the logger. Write down what each sensor is for and where it goes, how its readings get out when the internet or the power fails, who gets the alert and what they do, how long the record is kept, and how you will test the system before you rely on it. Then ask every supplier to answer that same specification.

How to use this guide

  1. Step 1: Decide what it answers

    One purpose and one position for every sensor.

    Go to What to measure
  2. Step 2: Ask every supplier

    The same questions on outages, alerts, records and calibration.

    Go to Supplier questions
  3. Step 3: Test it at handover

    Fill in the acceptance check before you rely on it.

    Go to the record

What does the monitoring have to answer?

Each sensor should answer one question. The answer decides what it measures and where it goes. The parts of a system and the main kinds are set out on our temperature monitoring page.

Match each sensor to the question it answers
The questionWhat to measureWhere it goes
Is the stock holding temperature?A product simulator: a probe in a small bottle of glycol or wax that follows the stock, not the air.Where stock sits in the warmest part of the room, found by probing first. Out of the cold air off the evaporator.
Has the refrigeration failed, and when?An air sensor, which shows a failure quickly.In the room's air, clear of the blast from the doorway.
Is a door being left open?A door contact.On the door and frame. It alerts when the door stays open longer than a set time.
Has the power gone off?The system's own lost-contact or power alarm.At the gateway or controller, on the same supply as the refrigeration.
Is anything near freezing that should not be?An air sensor with a low limit.In the coldest spot, where stock can be damaged by freezing.

A simulator and an air sensor answer different questions, and some systems use both: the air sensor to alarm quickly, the simulator for the record. The guide to food temperature and fridge readings explains why they read differently.

Wired, Wi-Fi, long-range radio or a mobile gateway?

What each way of getting readings out needs on site
ConnectionWhat the site needsWhat to watch for
Wired sensorsCable runs from each room to the logger or controller.Reliable, but costly to install and hard to change later.
Wi-Fi loggersStrong Wi-Fi at every room, and someone who looks after the network.Coolroom walls block short-range radio. A logger with its body outside and its probe through the wall on a lead is the usual answer. The installer makes and seals the entry through the panel.
Long-range radio (LoRaWAN) to a gatewayOne gateway with power and an internet or mobile connection.Battery life depends on reporting frequency and how cold the sensor runs. The probe goes inside on a lead.
A mobile data gatewayMobile coverage and power where the gateway sits.Some gateways carry a backup battery of up to about 24 hours and hold readings until the network returns. Check which networks it uses.

Test the signal from inside every room before you choose. A compressor nearby can also interfere with the radio.

When the internet, the mobile network or the power fails

A system that keeps recording through an outage protects the record, not the stock. Ask each supplier:

  • How long can the sensors and the gateway hold readings? Memory is finite. Sensors usually hold a few thousand readings, which at 5-minute logging is about one to three weeks, and some stop logging when they are full.
  • How soon does it alert on lost contact? Systems wait a set time before they report it, so that brief dropouts pass. A few minutes suits a gateway, because a gateway that goes quiet often means a power cut. Lost contact cannot tell a power cut from a dropped connection.
  • Is there an alarm on site? A light and a buzzer at the controller still work when the internet does not, and some controllers record each power failure and how long it lasted.
  • What keeps the gateway and the internet running? A gateway with a battery, or the router on an uninterruptible power supply, keeps readings and alerts going through a short blackout.

Then agree who is responsible while alerts cannot get through: who checks the rooms, how often, and with a probe in the food, until the system is back. Write it into your refrigeration contingency plan.

Alerts, people and several zones on one dashboard

  • Name every sensor by its equipment and place, the way your staff and your technician name them: "Kitchen coolroom, back shelf", not "Sensor 3". Match the names to your equipment list.
  • Give every zone an alert group. On some systems an alarm with nobody in its group only changes a colour on the dashboard.
  • Escalate. Tell the first person straight away, and a second group if nobody has responded after a set time, such as an hour.
  • Separate who acts from who needs to know. The people who can go and do something get the phone alert. One person acknowledging an alarm can silence it for everyone, so agree who does.
  • Split the jobs. Staff respond to temperature alarms, and someone else owns batteries, calibration and the subscription.

Is door-open monitoring worth it?

In a busy coolroom, often yes. A door contact shows when and for how long the door was open, and alerts when it stays open too long while ignoring short openings. That record explains temperature rises: a door left open gives a faster rise than a power cut, and a restock alone can trip an alarm. It also shows out-of-hours access, and doors held open waste energy. Some controllers with a door switch hold off the temperature alarm while the door is open, so check how the two work together.

A remote farm coolroom or a marine ice store

At a remote room, decide first who acts on an alert, and how long they take to get there. A buzzer nobody hears is no help, so the alert has to reach a phone.

  • Coverage. Check mobile coverage where the gateway will sit, not at the house. A mobile gateway suits a room with no internet.
  • Power. The gateway needs power, ideally with a backup battery, so readings and alerts keep coming through a power cut. Ask whether it also reports the loss of mains power.
  • What to watch. For an ice store, decide whether you need the store's temperature, a warning that the machine has stopped, or both, and who acts when the premises or the boat is unattended.

Questions to put to every supplier

Questions to ask, and why each matters
AskWhy it matters
How accurate are the sensors?Loggers commonly state 0.3°C to 1°C accuracy. A food business's instrument has to be accurate to within 1°C.
What calibration certificate comes with it?A certificate from a NATA-accredited laboratory (ISO 17025) and a "traceable" certificate are different things, and a maker's certificate of compliance is not a calibration of your logger. Calibration usually checks three temperatures. Ask what happens to your monitoring while sensors are away.
How often does it log?Too slow a log hides how long a rise lasted. Loggers usually record every 5 to 15 minutes. Safe Food Victoria's guide for food premises suggests a reading every 30 minutes to an hour and leaves the choice to the owner, so ask what the system uses and whether you can change it.
Can the logger body take the cold?Some are rated only to about -23°C, so freezers need an external probe. Batteries in deep cold need a low-temperature cell.
How long is the history kept, and how do you get it out?Ask for the retention period, export as PDF and as CSV or Excel, and whether readings can be edited. Set up a regular export to your own storage.
Who owns the data, and what if you stop paying?Some systems run only in the supplier's cloud and treat the data as theirs. Ask how you would get a full copy.

Records, validation and calibration

Standard 3.2.2A (opens in a new tab) asks category one businesses, in short a caterer or food service business that makes unpackaged, ready-to-eat, potentially hazardous food, to make a record that shows they have managed the food safety risks when they do a prescribed activity, and to keep it for at least 3 months. Food Standards Australia New Zealand counts a data logger graph as one such record. Our temperature monitoring page sets out the rest of the rule, including when a record may not be needed. In Victoria, Safe Food Victoria (opens in a new tab) accepts remote monitoring as an alternative to twice-daily probe checks, provided the system reports at least twice a day, alarms when a unit is not holding temperature, records corrective actions, reads to within plus or minus 1°C, is validated, is calibrated each year, and is maintained. What a daily record holds is in the guide to a temperature record sheet for a commercial coolroom.

Its guide for food businesses sets the acceptance test. For a new system, keep doing twice-daily probe checks of the food for 30 days alongside it and compare. Infrared readings do not count for this. Map the hot and cold spots with a probe before the sensors go in. The installer and the manager sign the system off, a map shows which units are not on it, and the validation records are kept for two years. The guide was written for Victorian class 2 food premises, and its alarm delay of up to 30 minutes stops brief rises from triggering an alarm.

Mapping a new room before you load it

A new coolroom or freezer room is not one temperature, so find out where its warm and cold spots are before stock goes in. The most detailed published method is the World Health Organization's guidance on temperature mapping (opens in a new tab), written for walk-in medicine stores rather than reach-in cabinets. Adapted for a food coolroom, it comes to this:

  1. Use loggers of one type, all started at the same time, logging every 1 to 15 minutes.
  2. Place them where stock will sit, low, middle and high, plus the centre if pallets go there.
  3. Run the room empty, and again loaded the way you will stock it, for 24 to 72 hours each.
  4. Plan the door openings in advance and log every opening and any power cut.
  5. Use the result to place the permanent sensor and to mark any spot where stock should not sit.
  6. Map again after a big change, such as a new set point, a new layout or new refrigeration.

Monitoring specification and acceptance check

Monitoring specification and acceptance check

Fill in the specification before you ask for quotes, and the check when the system is handed over. Copy it or print it.

Your answers stay on this open page. They are not saved or sent. Copy or print them before you leave.

The specification

Connection

The acceptance check at handover

Every sensor named to match the equipment list
Test alarm reached the first and second groups
Lost-contact or power alarm tested
Alarm on site works
New rooms mapped before loading
Export tested and saved
Calibration certificates received

Who to call

We install temperature monitoring and alarms for coolrooms, freezer rooms and commercial fridges in Bairnsdale and East Gippsland, and we repair the refrigeration they watch. Our temperature monitoring page explains how to get a system set up: send the specification above with your enquiry. When an alarm turns out to be a fault, our coolroom and commercial fridge repairs page explains how to book.