Commercial fridge error codes: identify the model before you read a code
Why one code means different things on different fridge controllers, what to record before an alarm clears, and an alarm report to send the technician.
Last updated
Commercial fridge error codes are not universal. A code means what the manual for that model and its controller says it means, and the same letters can mean different things on two controllers: HA is a live high temperature alarm on one and a saved record of an earlier one on another, and E1 can be a failed probe or a fault in the controller itself. So before anyone presses a button, record the message exactly, with the model from the plate, the time and the temperatures. Then read it against the manual for your model, and call us.
How to use this guide
Step 1: Record it first
A photo, the exact message, the model, the time and the temperatures.
Go to What to recordStep 2: Fill in the alarm report
Add what the manual for your model says, and what happened before.
Go to the record
Why does the same code mean different things?
A coolroom or commercial fridge shows codes from its controller, the electronic unit that runs the refrigeration, shows the temperature and signals alarms. Each controller maker writes its own code list. Cabinet makers then set the controller up for their own equipment, which can change what an input or an alarm is used for, and a maker can change a product without notice. So a code on its own tells you very little.
The two tables below show three controllers from three makers, each read from its own current manual. They are examples, not a list to read your own display against. ABL does not speak for any of these makers, and the manual for your model is the reference.
| On the display | Controller A | Controller B | Controller C |
|---|---|---|---|
| HA | A high temperature alarm: the temperature is above its high limit now. It clears itself once the temperature is back to normal. | A saved record that the temperature stayed above its high limit for longer than a set delay. It keeps the time and the highest temperature, and stays on until it is reset. | Not one of its codes. |
| dA | The door has been open for longer than its set delay. | An alarm from an outside contact, after a delay. What that contact is depends on how the controller was set up. | Not one of its codes. |
| E1 | Not one of its codes. Its probe faults show as P1 and P2. | The defrost probe has failed. | A fault in the controller itself. |
| The defrost light flashing | Water is draining off after a defrost. | A defrost is due but is being held back. | All its lights flash together when there is an alarm. |
| What is happening | Controller A | Controller B | Controller C |
|---|---|---|---|
| The temperature is above its high alarm limit | HA | HI | A1 |
| The door has been open too long | dA | dor | A4 |
| The main temperature probe has failed | P1 | E0 | E29 |
| A defrost is running | The defrost light is on. By default the display holds the temperature from when the defrost started. | dEF, with the defrost symbol lit. | -d-, which can stay on the display for up to 15 minutes after cooling starts again. |
Software matters too. One of these manuals states the software version it covers, and another notes that one firmware version changes what a symbol on the front shows. So use the manual that matches the model number on the plate, and note its date or revision. If you do not have it, whoever you contact will ask for the model and serial number, so have both ready. If you cannot find the manual, record the message anyway and leave the meaning to us.
What should you record before anything is cleared?
Write it down before anyone presses a button. A code can go away on its own or with one press, and the clue goes with it:
- Many alarms clear themselves once the condition passes. On controller A, a temperature alarm stops as soon as the temperature is back to normal, and a probe alarm stops seconds after the probe works again.
- Some controllers hold several codes and show one at a time. On controller C, a fault code hides a temperature alarm until the fault clears.
| Record | How |
|---|---|
| A photo of the display | Take it from where you would normally stand, with the whole display in the frame. A short video catches a code that flashes. Do not open a panel, move the unit or reach behind it. If any sign in the warning at the top of this page is present, leave the photo and follow the warning. |
| The exact message | Every letter, number, dot and dash, as it appears. Whether it flashes or stays steady, which lights or symbols are on, whether the buzzer is sounding, and any other code that shows in turn. |
| The model, serial and controller | From the plate or rating label. On a cabinet it is usually inside, on a side wall, and on some models at the back as well: use the one you can read without moving anything. If the controller has a name or model on its front, note that too. Do not go into a menu to find it. |
| The time | When the message was first seen, and by whom. If it has already cleared, when it went. |
| The readings now | The temperature on the display, and the food temperature from a probe thermometer in the thickest part of the food, with the time of each. |
| What happened before | The door, deliveries, cleaning, a power cut or a storm, a service visit, and anything moved or changed in the last day or so. |
The alarm report further down has a place for each.
Is it a notification, a fault or a food decision?
Messages come in three kinds, and each goes to a different person. Controller C sorts its own codes this way: status codes for what it is doing, alarm codes for something in daily operation, and fault codes for a defect. The manual for your model says which kind a code is.
| Kind | Examples | What it tells you | Who acts on it |
|---|---|---|---|
| A notification | A door left open, a defrost in progress, an energy saving mode, a cleaning or standby mode. | The equipment is doing what it was set up to do, or telling staff about something they did. | Staff: close the door, or let the defrost finish. If the message stays longer than the manual says it should, treat it as a fault. |
| A refrigeration fault | A failed probe, a fault in the controller, a high condenser temperature, a pressure or refrigerant system alarm, a supply voltage alarm. | Something in the equipment needs a technician. Some faults leave the unit running on a timer, so it may still be cooling. | A refrigeration technician. Book a repair. |
| A temperature alarm | A high or low temperature alarm. | The air at the probe passed a limit for longer than a delay. Both are settings chosen for the equipment. | Your food safety procedure decides about the food, from probe readings. A technician finds out why it happened. |
An alarm limit is not the food rule
Alarm limits and delays are settings. Factory high limits range from 8°C with a 30 minute delay to a limit so high that the alarm will not sound on a warm fridge unless someone lowered it, and some cabinets wait up to two hours before alarming, so that door openings do not set the alarm off. An alarm that has not sounded does not mean the food is cold enough.
Under Standard 3.2.2 (opens in a new tab), as Safe Food Australia explains it, potentially hazardous food is kept at 5°C or below or at 60°C or above, unless the business can show that another temperature is safe, and frozen food stays frozen. That rule is about the food, so the reading that counts is the food's. Food Standards Australia New Zealand (opens in a new tab) says temperature gauges on refrigerators measure the equipment's temperature, and to use a probe thermometer to be sure of the food's. For how the two readings differ, see the guide to food temperature and fridge readings.
Can you reset or silence it yourself?
Leave that to the technician. Do only what the manual for your model gives the owner to do, and within that, only what changes nothing in the equipment:
- Close the door properly, and see that nothing is holding it open.
- Move stock that is blocking the air vents inside.
- Check the food with a probe thermometer, and follow your food safety procedure.
- Let a defrost finish. Its message can stay for a while after cooling starts again.
Leave the rest alone, even where your manual describes it:
- Do not reset an alarm, or clear a code with a button or a combination of buttons.
- Do not go into a settings, service or history menu.
- Do not change the set temperature or any other setting.
- Do not start a manual defrost.
- Do not switch the unit off and on again to clear a code.
- Do not take off a grille or cover to clean a filter or a condenser. That is service work.
- Do not bypass a door switch, a probe or any other safety device.
Silencing the buzzer fixes nothing. On controller B, the button that silences it also switches off the alarm output, and on controller C a brief press to acknowledge an alarm does the same. On one cabinet, the silence button clears the code from the display. So write the report before anyone touches the keypad.
Does a cleared alarm mean the problem has gone?
No. A code that clears tells you the condition has passed for now. It does not show that the cause has gone, or that the food is safe.
- The fault can come back. On controller A, a probe alarm stops seconds after the probe works again, so a probe that fails now and then gives an alarm that comes and goes. If it keeps happening, see the guide to recording intermittent refrigeration faults.
- A code can be about the past. Controller B's HA stays on after the temperature has come back, as a record that it was too warm. Note it and its time.
- The air recovers before the food. A display back to normal means the air at the probe is inside its limit again. It says nothing about food that warmed while it was out. The air also warms when a door opens or a defrost runs, and during a defrost controller A by default holds the reading from the start of the defrost.
So probe the food, write down each reading with its time, and follow your food safety procedure. The coolroom and commercial fridge repairs page sets out the food safety points that procedure rests on. If your staff keep a daily temperature record, the guide to commercial refrigeration temperature records has a sheet for it.
Alarm report
How urgent is it?
| What you see | What to do |
|---|---|
| A burning smell, a tripped breaker or water near the electrics, with the alarm | Follow the warning at the top of this page: turn it off, leave it off and call. |
| Food probes above 5°C, or frozen food has started to thaw | Your food safety procedure decides what happens to the food, and the repairs page sets out the food safety points it rests on. Then call. |
| A fault code, such as a probe or controller fault | Call to book a repair, and send the alarm report. The unit may keep running on a timer, so keep probing the food. |
| A temperature alarm that stays once the door is shut | Probe the food and call. |
| A notification that does not clear when the manual says it should | Treat it as a fault. Record it and call. |
| A code that came and went | Record what you saw and when, and tell us when you next call or book a service. |
What we do with your report
We read the message against the manual for that model and its controller, and look at any alarms the controller has saved. We find the cause before anything is reset. Your report shows us what the display said before anyone touched it, which the controller may no longer show.
To book the repair, see the coolroom and commercial fridge repairs page. If you want alarms that reach you by SMS or email when nobody is on site, and a temperature record that builds itself, see the temperature monitoring page.
Sources (13)
- Dixell: XR06CX digital controller instruction manual, r1.2, 27 July 2015 (controller A) (opens in a new tab) Checked on 19 November 2026.
- CAREL: ir33 platform user manual, release 2.5, 16 June 2010 (controller B) (opens in a new tab) Checked on 19 November 2026.
- Danfoss: EKC 202 controller for temperature control, user guide, October 2018 (controller C) (opens in a new tab) Checked on 19 November 2026.
- SKOPE: SKOPE-connect user guide (opens in a new tab) Checked on 19 November 2026.
- SKOPE: user manual for the SC112N-A four glass sided chiller, January 2022 (opens in a new tab) Checked on 19 November 2026.
- SKOPE: ReFlex series user guide, October 2021 (copy held by a retailer) (opens in a new tab) Checked on 19 November 2026.
- Williams Refrigeration Australia: operating manual for upright and counter refrigeration, April 2020 (copy held by a reseller) (opens in a new tab) Checked on 19 November 2026.
- Hoshizaki: Steelheart refrigerated prep table instruction manual, August 2020 (copy held by a retailer) (opens in a new tab) Checked on 19 November 2026.
- Bromic Refrigeration: semi vertical and full height multidecks instruction manual, June 2025 (opens in a new tab) Checked on 19 November 2026.
- Food Standards Australia New Zealand: thermometers, updated 1 October 2025 (opens in a new tab) Checked on 19 November 2026.
- Food Standards Australia New Zealand: Safe Food Australia, chapter on Standard 3.2.2, revised April 2026 (opens in a new tab) Checked on 19 November 2026.
- Australian Government: Triple Zero (000) (opens in a new tab) Checked on 17 November 2026.
- ABL Refrigeration: commercial refrigeration services (opens in a new tab) ABL's own page. Checked on 19 November 2026.
Related pages
- Coolroom and commercial fridge repairs in East Gippsland
Book the repair, and what to do with the stock.
- Food temperature and fridge readings: understanding the difference
Why the display and the food read differently.
- Recording intermittent commercial refrigeration faults
If the alarm comes and goes before anyone can look.
An alarm on a coolroom or commercial fridge?
Call ABL with the message, the model from the plate and the food temperatures, or send the alarm report with an enquiry.