Repeated condensate alarm on commercial air conditioning: what to record
Why a condensate or drain pump alarm on commercial air conditioning keeps coming back, what to record each time, and who looks after the pump.
Last updated
The alarm usually means the water the air conditioner makes is not leaving fast enough, and the high-level float switch has stopped the unit, or warned you, before the tray overflows. An alarm that keeps coming back has a cause that has not been found, and clearing it again only puts more water into a drain that is not coping. Record which unit, what the alarm says and how often, and have the drainage assessed.
How to use this guide
Step 1: Identify
Which unit, what kind of drain or pump it has, and the exact alarm.
Go to Identify the equipment
What is a condensate or drain pump alarm?
An air conditioner makes water whenever it cools. Moisture in the air condenses on the cold coil, collects in a tray under it, and has to leave the building. Some units drain through a pipe that falls all the way to a waste point or outside. Where the drain cannot fall all the way, a small pump lifts the water out first, either built into the unit or fitted beside it.
On a typical add-on pump, a float switch senses the water level and runs the pump, and a second, higher switch, the high-level float switch, sits above the normal level. A pump built into the unit, or a gravity drain with a float switch in its tray, can be arranged differently, and the manual for the model shows how. When water reaches the high-level switch, the unit stops cooling, raises an alarm, or both, depending on the equipment and how it was wired. So the alarm usually means that switch has done its job, and the question is why the water got that high.
| Usual cause | Who deals with it |
|---|---|
| The drain pipe is blocked, kinked or crushed | A technician. |
| The tray is dirty, or a float is dirty, stuck or faulty | A technician. |
| The pump has failed, or has no power | A technician, and a licensed electrician if the supply to the pump is at fault. |
| The pump is not sitting level, or is too small for the water the unit makes | A technician or the installer. |
| The drain has too little fall, too long a run or too high a lift | The installer, or a technician looking at the design. |
This guide does not decode alarm codes. The same code means different things on different brands, and a list for another model will send you the wrong way. The manual for the unit, and for the pump if it is a separate one, gives the meanings for yours.
Identify the unit, the drain and the alarm
Write these down once and keep them with your equipment records. You can get all of them without touching the unit.
| Identify | Where to find it |
|---|---|
| Which unit it is | Its label, its room, and what it serves. On a site with several units, an alarm with no unit named sends the technician looking. |
| Brand and model | The nameplate on the unit, the last service report or your equipment list. A photo is enough. |
| The kind of drain | Whether the unit drains by gravity, has a pump built in, or has a separate pump beside it. The handover documents or your maintenance provider can tell you. |
| Where the water goes | Where the drain ends: outside, at a waste pipe or at a gully. If nobody knows, write that down. |
| Where the alarm shows | On the wall controller, as a light on the unit, as a buzzer, or as a message on a building management system. |
| Exactly what it says | The code, the words and the pattern of any light, copied as shown. Photograph it before anyone clears it. |
| What the manual says | The page of the unit or pump manual that covers the alarm, if you have the manual. Note what it says, and tell the technician. |
What is at risk if it overflows
An overflow lands on whatever is below the unit or along its drain. Knowing what that is tells you, and the technician, how fast this has to be dealt with. Note:
- what sits under the unit and under the line of its drain: desks, stock, computers, a counter, a bed
- whether there are lights, power points or other electrical equipment in or under that ceiling
- whether water has shown before, and where: a stain, a drip, a swollen ceiling tile
- what the unit serves, and what stops if it stays off
- who is on site outside hours to notice an alarm overnight or at a weekend
If water has already escaped, the guide to water leaking through the ceiling near commercial air conditioning covers what to do and which trades to call.
What to leave alone
- Do not keep clearing the alarm. Each restart sends more water to a drain that is not coping.
- Do not bypass it. The high-level switch is what stands between a blocked drain and a wet ceiling. A unit running with that switch defeated can overflow with no warning.
- Do not pour anything into the tray or the drain, or push anything along the pipe. Shop-bought cleaning products can damage the parts inside an air conditioner and cause leaks.
- Do not open the unit or the pump, or lift ceiling tiles to look for them.
Who looks after a condensate pump, and what does its maintenance include?
A condensate pump is small, out of sight and easy to leave off everyone's list. A repeated alarm is often the first sign that nobody was looking after it. Settle these before the next one.
| Who | Responsible for |
|---|---|
| The business on site | Noticing and reporting an alarm, keeping the log, and making sure staff know not to clear it and carry on. |
| The owner of the equipment | Having it maintained. In a leased building, the lease usually says who owns and maintains each unit. Under a retail lease in Victoria, the Retail Leases Act 2003 overrides what the lease says about repairs and maintenance: the landlord must maintain the plant and equipment at the premises in the condition it was in when the lease was entered into, and the Victorian Small Business Commission (opens in a new tab) gives the air conditioning as its example. The exceptions include a repair that arises from the tenant's misuse, and an item the tenant may or must remove at the end of the lease. |
| The maintenance provider | Inspecting the tray, the drain, the pump and its floats at each service. |
| The installer | How the drain was run and the pump chosen, if the system is new or the alarm has been there from the start. |
| One named contact | A name and a phone number that staff call about this unit, in hours and out of hours. |
Maintenance of a condensate pump and its drain usually includes:
- the tray checked and cleaned
- the drain checked from the tray to where it ends, for blockage, kinks, fall and any trap
- the pump and its floats cleaned, and the floats checked to move freely
- a test with water, so the pump is seen to clear it and the high-level switch is seen to stop the unit or raise the alarm
A pump, its float and its tray are usually cleaned and checked at least once a year, and more often where the air is dusty or greasy. The manual for the pump sets the interval.
Check that your maintenance agreement names the pumps and drains as well as the units, and ask how they are checked. The guide to commercial maintenance agreements covers what an agreement should list, and the guide to a maintenance and reopening calendar covers when the checks fall in the year.
What will a technician do?
We start from your log, because the pattern narrows it down: an alarm only on hot, humid afternoons suggests a pump or a drain at its limit, and an alarm within minutes of start-up suggests a blockage, a stuck float or a pump that is not running. A visit for a repeated drain alarm usually covers the maintenance checks above, and also:
- the alarm history on the controller or the building management system, where one is kept
- how the unit and the pump sit
- whether the pump and the drain suit the unit and the run they were given
Ask for the finding in writing: what the cause was, what was done, and what would bring it back. If the cause was not found, you should be told so, because the alarm is then likely to return.
How urgent is it?
| What you see | What to do |
|---|---|
| Water has escaped, or is near anything electrical | Keep clear, leave the unit off and call now. |
| The alarm has come back after being cleared | Leave the unit off and call before it is next needed. The switch may already have stopped one overflow. |
| A first alarm, with no water showing | Leave the unit off, record it and book a visit. |
| No alarm, but the pump runs much longer or more often than it did, or is noisier | Note it and tell your maintenance provider before the next hot spell. |
Drain and pump alarm record
If it returns after a repair
If the alarm returns after a proper repair, ask whether the drain or the pump suited the unit from the start. A safety tray under a ceiling unit, with its own separate drain, is a common protection where the unit sits over something that cannot get wet, so ask about one too. If the unit is also old or has other faults, the guide to repairing or replacing a commercial air conditioning system covers how to weigh it.
Calling ABL
ABL repairs and services air conditioning for homes and businesses in Bairnsdale and East Gippsland. Call with your alarm record in front of you. Our commercial air conditioning page covers the systems we look after for businesses, the air conditioning repairs page explains how to book a fault, and our air conditioning services page lists everything else we do.
Sources (8)
- Daikin: drain up kit operation manual, K-KDU572KVE (opens in a new tab) Checked on 19 November 2026.
- Sauermann: Si-60 condensate pump installation instructions (opens in a new tab) Checked on 19 November 2026.
- ActronAir: installation and commissioning guide, variable capacity commercial ducted indoor unit, version 4 (opens in a new tab) Checked on 19 November 2026.
- Daikin: troubleshooting for split and multi-split air conditioners (opens in a new tab) Checked on 19 November 2026.
- Victorian Small Business Commission: repairs and maintenance under a retail lease (opens in a new tab) Checked on 20 November 2026.
- Energy Safe Victoria: storms and energy safety, reviewed 9 May 2024 (opens in a new tab) Checked on 19 November 2026.
- Australian Government: Triple Zero (000) (opens in a new tab) Checked on 17 November 2026.
- ABL Refrigeration: air conditioning services (opens in a new tab) ABL's own page. Checked on 19 November 2026.
Related pages
- Commercial air conditioning ceiling water leak: what to do
For water that has already escaped, and which trades to call.
- Commercial air conditioning maintenance agreement questions
How to make sure pumps and drains are on the maintenance list.
- Business air conditioning pre-summer maintenance calendar
When drains and pumps are checked through the year.
Drain alarm keeps coming back?
Leave the unit off and call ABL with your alarm record in front of you.
Filled in the record? Copy or print it first: it is not sent with a call or an enquiry.